Jump to main contentCall usAvailable 24/7/365

Mobile Chiller KM 50

-10℃ to +20℃

50kW cooling capacity at 7°C/12°C and 32°C
Speed-regulated fans
Integrated circulation pump and expansion
2-stage cooling capacity regulation
Mobil Chiller KM 50

Technical specifications

DescriptionUnitValue
Cooling capacity 7°C, 12°C and 35°C outdoor temperaturekW50
Dimensionsmm1955 x 1123 x 1954
Weight (transport)kg620(600)
Performance Levelsstep 0/100%
CoolanttypeR410A
Compressorstype2 x scroll
Connection round tripinch1 1/2
Pressure drop evaporateskPa38
Max Flowm3/h15
Electrical inputkW26.6
Power consumptionA51.1
VoltV/Hz/Ph400 / 50 / 3 (3P + PE)
Electrical connectionCEEPlug CEE 63A (3P + N + PE)
Sound pressure level at 10 mdB(A)47
Flowm3/h9.1
Maximum working pressurebar10